What voltage of surge protection should be used on inputs, outputs, readers and communications circuits?

Input circuits: minimum working/service voltage: 12 volts

Output circuits (switching DC): minimum working/service voltage: 30 volts

Reader data lines: minimum working/service voltage: 5 volts

Reader power: minimum working/service voltage: as required by reader

RS-232 communication: minimum working/service voltage: ±25 volts

RS-485 communication: minimum working/service voltage: ±7 volts

Ethernet (non PoE): minimum working/service voltage: 5 volts

PoE: minimum working/service voltage: 60 volts